MS5215 High Voltage Digital Insulation Tester
Test Voltage Range DC250V~5KV
Insulation Resistance 0.01M~5T Ohm
Good quality
Port: Shenzhen
Minimum Order Quantity: 1 Set/Sets The more the cheaper!
Supply Ability: 600 Set/Sets per Month
Payment Terms: T/T,Western Union,MoneyGram,Paypal
Contact SupplierPackaging Detail: 200mm*320mm*400mm,5kg
Delivery Detail: Less than 15 days!
MS5215 High Voltage Digital Insulation Tester
Features
·Checking the insulation of high-voltage electrical equipment (electric motor, transformer, and cable, etc)
·Test Voltage from 250V to 5000V.
·Insulation resistance up to 5TΩ
·Short Current up to 3mA.
·Auto Calculate PI (Polarization Index) and DAR (Dielectric absorption ratio).
·Step-Voltage Measurement
·Temperature measurement
·Temperature compensation for insulation Test
·Leakage Current measurement.
·Data Storage function and uploading to PC by USB2.0 Interface.
·Timer Function
·Power Supply: LR6 Battery * 6 / rechargeable battery NI/ Charger: Input Voltage 100V to 240V,
Frequency 50Hz to 60 Hz, output voltage 12V DC 3A
·Weight 2.5kg (not including Battery)
·Size 284mm(L) * 230mm(W) * 125(H)
Temperature compensation
Test Voltage
·Test Voltage Range DC250V to DC5KV
·Voltage Set:
Wide adjust: 250V, 500V, 1000V, 2.5kV, 5kV
Fine adjust: 250V to 1kV, step 25V, 1kV to 5kV, step 100V
·Accuracy: 5%
·Step mode: 500V, 1.0kV, 1.5kV, 2.0kV, 2.5kV
·Test Current 1nA to 3mA
Specification | ||
Set test voltage | Test range | Accuracy |
250 V DC | 0.01MΩ~ 2.5GΩ | ±(5%rdg+5dgt) |
2.51GΩ~ 250GΩ | ±(20%rdg+10dgt) | |
500 V DC | 0.01MΩ~ 5.0GΩ | ±(5%rdg+5dgt) |
5.01MΩ~ 500GΩ | ±(20%rdg+10dgt) | |
1000V DC | 0.01MΩ~ 10GΩ | ±(5%rdg+5dgt) |
10.1GΩ~ 500GΩ | ±(20%rdg+10dgt) | |
501GMΩ~ 999GΩ | ±(20%rdg+20dgt) | |
2.5 KV DC | 0.01MΩ~ 25GΩ | ±(5%rdg+5dgt) |
25.1GΩ~ 500GΩ | ±(20%rdg+10dgt) | |
501GΩ~ 999GΩ | ±(20%rdg+20dgt) | |
1TΩ~ 2.5TΩ | ||
5KV DC | 0.01MΩ~ 50GΩ | ±(5%rdg+5dgt) |
50.1GΩ~ 500GΩ | ±(20%rdg+10dgt) | |
501GΩ~ 999GΩ | ±(20%rdg+20dgt) | |
1TΩ~ 5TΩ |
Leak Current | ||
Range | Measuring range | Accuracy |
10nA | 1.00nA ~ 9.99nA | ±(15%rdg+1nA) |
100nA | 9.0nA ~ 99.9nA | ±(15%rdg+5dgt) |
1000nA | 100nA ~ 999nA | ±(2.5%rdg+5dgt) |
10uA | 0.90uA ~ 9.99uA | |
100uA | 9.0uA ~ 99.9uA | |
1000uA | 90uA ~ 999uA | |
3mA | 0.90mA ~ 3.00mA |
Voltage Test | ||
Test mode | DC voltage | AC voltage |
Test range | ±(50V TO 1000V) | 50V TO 750V (50Hz to 60Hz) |
Precision error | ±(5%rdg+5dgt) | |
Input resistance | Approx 10MΩ |
Temperature test | |
Measuring range | Measuring precision |
-10°Cto 0.1°C | ±1.5°C |
0.0°Cto 40.0°C | ±1.0°C |
40.1°Cto 70.0°C | ±1.5°C |