RB-TT Gas Detector Measuring range: 0-100%LEL
RB-TT Gas Detector Output signal: 4-20mA
Port: China Port
Minimum Order Quantity: 1 Set/Sets
Supply Ability: 500 Set/Sets per Week
Payment Terms: L/C,T/T
Contact SupplierPackaging Detail: packed with cartons, and according to customer's requirement
Delivery Detail: delivery in 10 days, and according to production arrangement
1, General Introduction
RB-TZy model and RB-TTy type Fixed Gas detector are developed with our latest technology with measuring range of 0-100% LEL. They are usually applied in continuous monitoring in inflammable gas content in air and installed in the location of gas leakage. It will transform the signal of inflammable gas into 4-20mA standard signal, and also be connected with PLC, DCS and Inflammable Gas Alarm Control Unit which are capable to read 4-20mA standard signal.
The detector is designed and manufactured in strict accordance with “GB15322.1-2033,” which stands for the Inflammable Gas Detector Part-1 with measuring range of 0-100%LEL, GB3829.1-2000, which stands for General Requirement for Electrical Equipment of Explosive Gas Conditions Part-1, GB3836.2-2000, which stands for explosive-proof d-type of Electrical Equipment of Explosive Gas Conditions Part-2. They passed the National Inspection for explosive-proof features and functions, of which the certificate No. of Explosive-proof are CNEx11.0406X and CNEx11.0405X.
The product can generally be applied in the field of petrochemical, oilfield, oil depot, liquid gas stations, mining, environmental protection and fire-fighting, etc. It is the ideal gas detector that guarantees personal property and safety.
2, Technical Specification
1,Detectible gas: hydrogen
2,Measuring range: 0-100%LEL
3,Accuracy: ≤±5%F.S
4,Output signal: (4-20)mA
5,Operation power voltage: DC24V
6,Power consumption: 1.5W
7,Operation Environment:
Temperature: -40°C~70°C
Humidity: ≤93%RH
8,Air pressure: 86kPa -106kPa
9,Insulation resistance: normal environment ≥100MΩ
When humidity is 93%RH≥1MΩ
10,Working manner: continuous
11,Explosive-proof type: Exd
12,Measuring type: diffusion
13,Storage
Temperature: -50°C~80°C
Humidity: ≤95%RH
14,Product life: 3 years
15,Size: 175mm×145mm×98mm(RB-TZy)
70mm×95mm×110mm(RB-TTy)
3, Detection Structure Introduction
Type Structure | RB-TZy | RB-TTy |
Plastic Housing | The detector has qualified explosive-proof metal housing, including 1 housing, 1 top cap and one aluminium detecting housing, in the side face of which has 1 metal connector for wires connection. | The detector has qualified explosive-proof metal housing, including 1 housing and 1 top cap, in the side face of which has 1 metal connector for wires connection. |
PCB | PCB is installed in the housing, connected with controller with binding post for convenient connection. | PCB is installed in the housing, connected with the connectors for convenient connection. |
Sensor | The sensor is fixed in the side face of aluminium detecting housing | The sensor is fixed in round-shape copper net of top cap. |