Home  >  Electrical Instruments  >  Energy Meters

three phase Kwh meter with RS485 PZ80L-E3/C - PZ80L-E3/C

Measure all the data of 3 phase, CE MARK (EMC, LVD), RoHS Mark, Size: 80x80mm, With RS485 interface for communication - more info check here: http://www.buymeasuringtools.com/three-phase-Kwh-meter-with-RS485-PZ80L-E3-C-10046853/

Quick Brief

Place of Origin: Shanghai China (Mainland) Brand Name: ACREL Model Number: PZ80L-E3/C Display Type: Digital Only Phase: Three Phase Accuracy Class: 0.2S,0.5S Operating Temperature: -10C ~ +45C Dimensions: 80*80mm EN 61326:2006: EN 61010-1:2001

Product Features:

Measure all the data of 3 phase

CE MARK (EMC, LVD), RoHS Mark

Size: 80x80mm

With RS485 interface for communication

Business Terms:

Port: Shanghai

Minimum Order Quantity: 1 Piece/Pieces

Supply Ability: 100000 Perch/Perches per Year

Payment Terms: L/C,T/T

Contact Supplier
three phase Kwh meter with RS485 PZ80L-E3/C
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: PACKED BY CASE

Delivery Detail: within 2 weeks

Specifications and Product Details:

1. General

PZ80L-E3/C Series power analyzer specializes in measuring the data of all kinds of AC networks, such as the currents, the voltages, the powers, the energies etc... It may be used for local display, or it is connected with the control equipment in measuring and controlling system.

They are a kind of programmable analyzer. With the 4 key on the front, we can set their parameters according to the network which we measure. They have many option functions. They can be equipped RS-485 communication with Modbus-RTU protocol; or they can output analog signal or relay signal.

They are a kind of analyzer with excellent cost performance, since they regroup the functions of traditional electric transmitter and digital meters. Therefore they are widely being used in kinds of control system, SCADA system and power management system.

2. Technical parameters

Technical parameters

Value

Input

NetworkSingle-phase network; 3-phase balanced network

3-phase unbalanced, 3 wires; 3-phase unbalanced, 4 wires

Measurable26 parameters (3I, 6U, F, 4P, 4Q, 4cos, 4E)
Frequency45 ~ 65Hz

Voltage

AC 100V, 400V (programmable)
Overload: 480V (continuous); 800V during 1s
Consumption: < 0.2VA

Current

Rating: AC 1A, 5A (programmable)
Overload: 6A (continuous); 50A during 1s
Consumption: < 0.2VA
Thermal drift<200ppm

Transformation ratio

Programmable

Options

Analog output

1 or 2 outputs, 0 ~ 20mA, 4 ~ 20mA programmable
Load capacity: ≤500Ω

Logic output (DO)

2 relays NO contact outputs (for remote terminal)
Contact capacity: AC 250V/3A, DC 30V/3A
Alarm outputthe alarm of over voltage, under voltage and over current
CommunicationRS485 (Modbus-RTU protocol)
Logic input (DI)2 or 4 dry contacts (with 5V power)

Pulse

2 pulse outputs (open-collector),
Pulse constant: 10000, 40000, 160000 imp/kWh
DisplayLED, LCD

Precision

0.5 (F: 0.05Hz; kVar: 1)

Power supply

AC/DC 85 ~ 270V; Consumption ≤ 4VA

Test voltage

2kVAC/min (voltage input / power; between current inputs)
1.5kVAC/min (outputs / power)

Insulation

input / housing and output / housing >100MΩ

Environment

Work T: -10°C ~ +45°C
Storage T: -20°C ~ +70°C
Relative humidity: 5% ~ 95% (no condensation)
Altitude: ≤2500m

3. Options
- Communication (/C) : RS485 (Modbus-RTU);

1 start bit, 8 data bit, 1 stop bit, no parity,

speed (1200/2400/4800/9600/19200)
- Alarm output(/J): 1 passive relay (1A/30VDC, 1A/250VAC):

alarms of over voltage, low voltage and over current;

The hysteresis and the delay can be set
- Analog output(/M): DC4 ~ 20mA, DC0~20mA (load < 600Ω),

DC0 ~ 5V,DC1 ~ 5V (load > 1kΩ)
- Logic options(/K): 2DI/2DO;

DI: dry contact Input, supplied inside, optoisolator;

DO: NO-NC contact; 1A/30VDC,5A/250VAC ( to control other equipments)

4. Order examplee
Before your order, please inform us the range of current inputs and voltage inputs and options you need.
For example:
Need the 3 phase 80 model ammeter with RS485 communication, 2DI/2DO and LCD display, the range of current is 0-5A
The product type is PZ80L-E3/KC

5. Free Software

Use our free software to realize reading or setting our power analyzers on computer. (Please download free software on our website)

Other size: 72x72mm, 80x80mm,120x120mm, 144*144mm

three phase Kwh meter with RS485 PZ80L-E3/C suppliers    three phase Kwh meter with RS485 PZ80L-E3/C manufacturers