1. smart DIN rail mounting temperature transmitter/transducer
2. width:12mm
3. programmable
4. output: 4~20mA 1~5V etc.
Port: Tianjin
Minimum Order Quantity: 5 Piece/Pieces
Supply Ability: 3000 Piece/Pieces per Month
Payment Terms: L/C,T/T,Western Union
Contact SupplierPackaging Detail: standard package paper carton
Delivery Detail: 4 weeks
R5T series intelligent digital thermocouple temperature transmitter, are used for industrial automation system, receive on-site thermocouple signal input, convert it to analog signal output with the same proportion and corresponding temperature, then isolate and transfer to DCS/PLC, which finally realize the temperature gathering and transmitting in industrial field, meanwhile meet with signal types matching, isolation, interference rejection and improve the system stability function between DCS/PLC. Input and output signals of products in this series can change range through software, adjust through digitization, automatically dynamic calibration zero, automatically cover temperature drift and other functions. This product contains one in-one out, one-in two-out, two in-two out a variety of combination forms. Width of the shell is only 12mm, which satisfies high-density on-site installation.
General specifications | |
Construction | Ultrathin terminal connection |
Connect | Phoenix terminal M3 screw |
Wire diameter | 0.2-2.5mm2 |
Tightening | 0.5-0.6Nm |
Housing material | Fire resin |
Protection grade | IP20 |
Mounting | EN60715 Standard 35mm DIN rail |
Dimensions | W12 x H95 x D110 mm |
Weight | approx. 100g |
Input signal specifications | |||||||
Input signal range | R temperature measuring scope:--40°C ~ 1700°C S temperature measuring scope:--40°C ~ 1700°C K temperature measuring scope:--150°C ~ 1370°C J temperature measuring scope:--80°C ~ 900°C | T temperature measuring scope:-160°C ~ 390°C B temperature measuring scope:-320°C ~ 1820°C E temperature measuring scope:--80°C ~ 700°C | |||||
Range of wire resistance | ≥10MW | ||||||
Minimum measure range | R: 600°C S: 600°C K:120°C J:100°C | T:100°C B:780°C E:500°C | |||||
Cold junction compensation | internal cold end compensation |
Typical application field:
Ø Transfer thermocouple or millivolt voltage signal into isolated standard signal.
Ø Field existing grounding potential difference.
Ø Field existing heavy electromagnetic interference.
Ø Protecting DCS or PLC system.
Ø Distributing one signal in two ways.