1. General
PZ96 Series single phase current meter or voltage meter are the programmable meter. Users can set the parameters according to different measured network by the 4 keys on the front panel. They can also transmit the measured data by RS485 communication and by analog output. At the same time, they can be equipped the logic input or output to realize remote control or alarm.
2. Specification
PZ96-AI Current meter PZ96L-AI Current meter with LCD display PZ96-AV Voltage meter PZ96L-AV Voltage meter with LCD display | /C : Option R485 /J : Option alarm output /M : Option analog output /K : Option logic input or logic output |
3. Technical parameter
Technical | Value | ||
Input | Range | voltage: AC100V, 220V, 380V; current: AC1A, 5A; | |
Overload | voltage: 480V(continuous), 1000V/30s; current:: 6A (continuous), 50A/1s | ||
Frequency | 45Hz~65Hz | ||
Consumption | < 0.5VA | ||
Accuracy | 0.5 | ||
Output | Display | LED or LCD | |
RS485 /C | Modbus-RTU | ||
Alarm /J | the alarm of over voltage, under voltage and over current | ||
Analog /M | DC4~20mA, DC0~20mA (R < 600Ω), DC0~5V (R > 1kΩ) etc. | ||
Pulse | 2 pulse outputs (open-collector), | ||
Pulse constant : 15000 imp/kWh, 15000 imp/kvarh | |||
Logic | Input | 2 or 4 dry contacts (with 5V power) | |
output | 2 relays NO contact outputs (for remote terminal) Contact capacity: 1A/30VDC, 1A/250VAC | ||
Power supply | Voltage range | AC85~265V or DC110-350V | |
Consumption | < 1.2W | ||
Insulation resistance | ≥ 100MΩ | ||
Insulation | Power / Input / output 2kV/1min(RMS) | ||
ENV | Temperature | Operation: LCD: -10°C~+45°C; LED: -10°C~+55°C Storage : -20°C~+70°C | |
Humidity | ≤ 93%RH, no condensation, without corrosive gas | ||
Altitude | ≤ 2500m |