Resonant voltage withstand test system, special for capacitor type voltage transformer testing, variable-frequency, series type
Port: Shanghai
Minimum Order Quantity: 1 Set/Sets
Supply Ability: 100 Set/Sets per Month
Payment Terms: L/C,T/T
Contact SupplierPackaging Detail: wooden case
Delivery Detail: within 30 days
This variable-frequency series-resonant voltage withstandtest equipment is special for checking CVT (capacitor type voltage transformer).
This kind of resonant test system satisfies step-up requirements by big capacity CVT checking. It adopts several reactors series connecting method, and so it is small volume, light weight.
The reactor can be fixed type or adjustable type, according to requirement.
II Main technical index
No. | Item | Data | |
1 | Ambient temperature | 10°C~+40°C | |
2 | Relative humidity | Less than 90% | |
3 | Working frequency | 50Hz | |
4 | Input voltage | AC220 (single phase) | |
5 | Distortion factory of output voltage wave | Better than 0.5% | |
6 | Rated input capacity | 2 reactors | 5kVA |
4 reactors | 5kVA | ||
6-8 reactors | 10kVA | ||
7 | Rated input voltage | 220V (four reactors) | |
8 | Rated input current | 22.7A / 45.4A | |
9 | Rated output voltage | 2 reactors | 76.2kV |
4 reactors | 152.4kV | ||
6 reactors | 209.6kV | ||
8 reactors | 303.1kV | ||
10 | Rated output current | 0.5A / 1A | |
11 | Withstand voltage of single reactor | 40kV / 60kV | |
12 | Capacity of single reactor | 20kVA / 40kVA / 60kVA | |
13 | Weight of single reactor | 45kg / 60kg |
III Configuration of ZXZ series test system
Code | 35/0.5 | 66/0.5 | 110/0.5 | 110/1 | 220/0.5 | 220/1 | 330/0.5 | 330/1 | 500/0.5 | 500/1 |
Capacity of control panel | 5kVA | 5kVA | 5kVA | 5kVA | 6kVA | 10kVA | 10kVA | 15kVA | 10kVA | 15kVA |
Rated voltage | 24.2 | 45.7 | 76.2 | 76.2 | 152.4 | 152.4 | 209.6 | 228.6 | 303.1 | 346.4 |
Rated current | 0.5A | 0.5A | 0.5A | 1A | 0.5A | 1A | 0.5A | 1A | 0.5A | 1A |
No. of reactors | 1 | 1 | 2 | 2 | 4 | 4 | 6 | 4 | 8 | 6 |
Withstand voltage of single reactor | 40kV | 50kV | 40kV | 40kV | 40kV | 40kV | 60kV | 40kV | 40kV | 60kV |
Capacity of single reactor | 20kVA | 25kVA | 20kVA | 40kVA | 20kVA | 40kVA | 20kVA | 60kVA | 20kVA | 60kVA |
Suitable CVT voltage | 35kV | 66kV | 110kV | 110kV | 220kV | 220kV | 330kV | 330kV | 500kV | 500kV |
Suitable CVT capacitance (μF) | ≤0.04 | ≤0.04 | ≤0.02 | ≤0.04 | ≤0.01 | ≤0.02 | ≤0.0075 | ≤0.0015 | ≤0.005 | ≤0.01 |