Features
1) Auto decimal shifting in KW and KWh.
2) Reverse phase indication on display.
3) KWh reset facility....
Port: shenzhen
Minimum Order Quantity: 1 Set/Sets other
Supply Ability: 8000 Set/Sets per Month 9H/D
Payment Terms: L/C,D/A,T/T,Western Union,MoneyGram
Contact SupplierPackaging Detail: color box or as customer's requirements.
Delivery Detail: within one week.
Digital power meter
All our instruments fulfill all important requirements and regulations concerning electromagnetic compatibility and safety isolation (IEC61000, IEC1010 standard and EN61010 standard). The devices have been developed, manufactured, and tested in accordance with Quality Assurance System ISO 9001.
No. | Variables | Unit | Direction | Display (Max.) | Accuracy |
1 | Current | A/kA | 9.999 kA | Class 0.2 | |
2 | Active Power | kW/MW | Directional | 20mA | Class 0.5 |
3 | Reactive Power | kVar/MVar | Directional | 20mA | Class 0.5 |
4 | Active Energy | kWh | Directional | 999999.99 MWh | Class 1.0 |
5 | Reactive Energy | kvarh | Directional | 999999.99 Mvarh | Class 2.0 |
Note 1. DEM8900-1 measure current, active energy, active power (optional, with analog output)
2. DEM8900-2 measure current, reactive energy, reactive power (optional, with analog output)
3. DEM8900-3 measure Current, active energy, reactive energy, active/reactive power (optional, with analog output)
The measured parameter unit is displayed on PC as follows
Measured Parameter | Current | Active Energy | Reactive Energy |
unit | A/kA | kWh/MWh | kvarh/Mvarh |
Parameter | Scope | Remark |
Meter address | 1—247 | |
PT | 1.00—99.00 and 100.0—6500.0 | |
CT | 1.0—6500.0 | |
RS485 baud rate | 2400 /4800/9600/19200/38400 | bps |
Pulse Energy Constant | 1—9600 | Passive pulse |
Pulse width | 20—100 | ms |
Analog output corresponding | 4—20mA or 0—5V | Corresponding value I1/I2/I3/P/Q |
Mult-tarrif rate | 2—12 Interval /alternation time is multiply by 30 minutes |
Parameters setup refer to operation instruction.
1.4 EMC and Safety standard
IEC61000-4-2 (GB/T17626.2)
IEC61000-4-8 (GB/T17626.8)
IEC61000-4-4 (GB/T17626.4)
IEC61010-1 (GB/T4793.1)
Update Date:2012-03-22 01:39:49