YOKOGAWA EJX115A Low Flow Transmitter
1.with BRAIN, HART, and FOUNDATION fieldbus communication protocols
Port: China port
Minimum Order Quantity: 1 Piece/Pieces
Supply Ability: 5000 Piece/Pieces per Year
Payment Terms: T/T,Western Union
Contact SupplierPackaging Detail: in carton
Delivery Detail: 6-7weeks
YOKOGAWA EJX115A Low Flow Transmitter
The EJX series is available with BRAIN, HART, and FOUNDATION™ fieldbus communication protocols.
The model EJX115A Low Flow Transmitter is a differential pressure transmitter assembled with an integral orifice and excellent for very low flow measurement. It outputs a 4 to 20 mA DC signal corresponding to the measured flow.
The orifice is available in six types with a bore ranging from 0.508 mm to 6.350 mm.
The combination of the bore selection with the differential pressure measurement span variation of the differential pressure transmitter enables a wide range of very small flow measurement.
The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage.
EJX115A Low Flow Transmitter | ||||
L Capsule | M Capsule | H Capsule | ||
Water equivalent | 0.016 to 7.2 l/min | 0.022 to 23 l/min | 0.07 to 33 l/min | |
Air equivalent flow | 0.44 to 198 Nl/min | 0.63 to 635 Nl/min | 2 to 910 Nl/min | |
Differential pressure span | 1 to 10 kPa (2 to 40 inH2O) | 2 to 100 kPa (8 to 400 inH2O) | 20 to 210 kPa (80 to 840 inH2O) | |
Accuracy | IFO | ±5% | ±5% | ±5% |
DP | ±0.04% | ±0.04% | ±0.04% | |
Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | |||
Certificates | FM, CENELEC ATEX, CSA, TIIS, IECEx | |||
Output | 4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication | |||
Supply voltage | BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type) Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model) | |||
Ambient temperature | -40 to 85 deg C (-40 to 185 deg F) (general use type) -30 to 80 deg C (-22 to 176 deg F) (with integral indicator) | |||
Process temperature | -40 to 120 deg C (-40 to 248 deg F) (general use type) | |||
Maximum working pressure | 16 MPa (2300 psi) | |||
Mounting | 2-inch pipe mounting | |||
Wetted parts material | Capsule | 316L SST (Diaphragm material is Hastelloy C-276) | ||
Manifold | 316 SST | |||
Cover flange | ASTM CF-8M | |||
Housing | Cast aluminum alloy or ASTM CF-8M stainless steel (optional) |