totalize,display, alarm control the flow parameters such as liquid,steam,natural gas,and general gas.
WT-400 series multi-flow rate totalizer(can with temperature and pressure compesation function)
Dimention: width×height×depth=80×160×125mm
Cut-out:76+0.7×152+0.7
application scope
cooperate with various sensors/transducers,
measuretotalize,display, alarm control ,transform output,
data receiving and communicate the flow parameters such as liquid,steam,natural gas,and general gas.
Function and feature:
Total automatic control,pressure compensation caculating,the compensation ways can be set at any way.
Linearity totalizing and radication totalizing setable.
Multi parameter display such as instant flow rate,total flow rate,temperature and pressre .
Small signal drop out function.dropping out ranges 0-0.5%selectively.
Totalized flowrate value can be reset by pushing button. The reset operation can be locked.
Off-power protection function,the total flow rate can be maintained more than 5 years as a result of off-power. All of the preset value is maintained for ever after off-power.
Advanced modular structure, with a powerful instrument chip, the functional combination and
system upgrade are very convenient.
major technique data:
the basic error: 0.5%FS or 0.2%FS±1 character
resolution: 1/20000, 14-digit A/D converter
display mode: Double liquid cristal display,the upper row with 4bits LED to display the instantaneous flow rate. The lower row 8-bit LED display the total flow rate.
sampling period: 0.5S
alarming output: instantaneous flow rate Two limit point alarm , relay output probe capacity AC220V/3A
transform output: 4~20mA, 0~10mA, 1~5V, 0~5V
accuracy: ±0.3%FS
communication output: Connection wayIsolation, serial bi-directional communicating connection RS485/RS422/RS232/Modem
baud rate:300~9600bps selectable
feed output: DC24V/50mA