Home  >  Electrical Instruments  >  Resistance Meters

USB Interface Pc Link Intelligent Earth Resistance Clamp Tester YH3002 - YH3002

Earth Resistance Clamp Tester YH3002, 1)Data storage,USB communication, 2)Test frequency: 94Hz/105Hz/111Hz/128Hz/AFC, 3)OEM - more info check here: http://www.buymeasuringtools.com/USB-Interface-Pc-Link-Intelligent-Earth-Resistance-Clamp-Tester-YH3002-10054827/

Quick Brief

Place of Origin: Guangdong China (Mainland) Brand Name: Earth Resistance Clamp Model Number: YH3002 Display Type: Digital Only Measuring Range: RK(wire compensation):Test fre... Testing Voltage: AC 20V/48V Accuracy Class: ±5% Operating Temperature: 0-40℃ Dimensions: 230*125*284mm Model: three models

Product Features:

Earth Resistance Clamp Tester YH3002

1)Data storage,USB communication

2)Test frequency: 94Hz/105Hz/111Hz/128Hz/AFC

3)OEM

Business Terms:

Port: Shenzhen Port

Minimum Order Quantity: 1 Piece/Pieces

Supply Ability: 5000 Piece/Pieces per Month More can be provided according to customers' need

Payment Terms: T/T,Western Union,MoneyGram

Contact Supplier
USB Interface Pc Link Intelligent Earth Resistance Clamp Tester YH3002
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: gift box for unit,carton box for outer

Delivery Detail: 5-7 days

Specifications and Product Details:

USB Interface Pc Link Intelligent Earth Resistance Clamp Tester YH3002

There are three models of this series, including Meter A, Meter B and Meter C, which can meet various requirements of different customers. The features are summarized in the following table.

Test modeFunctionsMeter AMeter BMeter C

3 pole & 4 pole earthing-resistance test

Test voltage: AC 20V/48Vyesyesyes
Test frequency: 94Hz/105Hz/111Hz/128Hz/AFCyesyes94Hz/128Hz
Earthing-resistance range0.02~ 3000.1~ 300.1~20

Selective mode

(3 pole +

4 pole+ )

Test voltage: AC 20V/48Vyesyes
Test frequency: 94Hz/105Hz/111Hz/128Hz/AFCyesyes
Earthing-resistance range0.02~200.1~10

Non-auxiliary-polar

mode ( )

Test voltage: AC48Vyesyes
Test frequency: 94Hz/105Hz/111Hz/128Hz/AFCyesyes
Earthing-resistance range0.02~1500.1~150

2 pole R-

Test voltage: AC20Vyesyesyes
Test frequency: 94Hz/105Hz/111Hz/128Hz/AFCyesyes94Hz/128Hz
Earthing-resistance range0.02 ~ 3000.1 ~ 300.1~20

2 pole /4pole R

Test voltage: DC20Vyesyes
Earthing-resistance range0.02~ 30.1~ 3

Interfering voltage

/current/frequency

Interfering voltage: 1~50V DC/ACyesyesyes
Interfering frequency: 16Hz~400Hzyesyesyes
Interfering current: 20mA~2Ayesyesyes

Soil resistivity

Test voltage: AC20V/48Vyesyesyes
Test frequency: 94Hz/105Hz/111Hz/128Hz/AFCyesyes94Hz/128Hz
Range: 0.02m~1000myesyesyes

RK(wire compensation)

Test voltage: AC20V/48Vyesyesyes
Test frequency: 94Hz/105Hz/111Hz/128Hz/AFCyesyes94Hz/128Hz
Range:0.02~300.1~300.1~30
Test currentless than 250 mAless than 100 mAless than 100 mA
Data storageyesyesyes
USB communicationyesyesyes