Home  >  Electrical Instruments  >  Energy Meters

Three Phase Multi Tariff Watthour Meter (RS485) - SDT872

Measure Multi Tarrif kWhs - 3-phase, 4 Tariffs and 8 time segments, Direct 100A input, RS485 with modbus, EN50222 & EN61000 - more info check here: http://www.buymeasuringtools.com/Three-Phase-Multi-Tariff-Watthour-Meter-RS485-10201113/

Quick Brief

Place of Origin: Shanghai China (Mainland) Brand Name: Standardel Model Number: SDT872 Display Type: Digital Only Phase: Three Phase Measuring Energy Range: 0-9999999 Accuracy Class: 1% Output Voltage: 5V Operating Temperature: -20~60C Dimensions: 7P Communication: RS485

Product Features:

Measure Multi Tarrif kWhs - 3-phase

4 Tariffs and 8 time segments

Direct 100A input

RS485 with modbus

EN50222 & EN61000

Business Terms:

Port: Shanghai

Minimum Order Quantity: 1 Set/Sets

Supply Ability: 10000 Set/Sets per Year

Payment Terms: L/C,T/T

Contact Supplier
Three Phase Multi Tariff Watthour Meter (RS485)
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: Case

Delivery Detail: One Week

Specifications and Product Details:

SDT872 Three Phase Multi Tariff Watthour Meter

1. General

SDT872 3-Phase DIN rail Energy Analyzers is the high accuracy energy measuring device. It is designed for Energy Management System(EMS). It can measure up to 4 energy tariffs and 8 time segements.
It has RS485 interface with Modbus protocol, to realize transfer the all energy data to master device; It has a energy pulse output to PLC or to pulse counter.
SDT872 is being used in many intelligent building, factories, universities, to realize the accurate energy count in time segments, so that it can save much electricity for users.

2. Functions

• Measure 1~4 kinds of different kWh tariffs and maximal 8 time segments;
• With 7 digits LCD;
• Input: Direct 3x5A, 3x16A, 3x32A, 3x63A, 3x100A;
• Line: 3P2L (2x110V/220V);
3P4L (3x120/220V, 3x220V/380V, 3x230V/400V);
3P3L (3x380V);
• With impulse outputs (kWh) and wire breakage alarm;
• With RS485 interfacer (Modbus-RTU protocol);
• Record all the energy data in Recently three months;
• With StandardeL PC software, the user may easily read and SDT872 data and program its parameters by computer.

3. Features:

Technical FeatureParameters
InputWiring2P3L, 3P3L, 3P4L
Voltage2x110V/220V,
3x120/220V, 3x220V/380V, 3x230V/400V,
3x380V
Rating: 0.9 ~ 1.1Un; maximal: 0.7 ~ 1.2Un
Consumption ≤5VA / line
Current3x5A, 3x20A, 3x32A, 3x100A
Minimal current 20mA
Minimal current 20mA
Consumption ≤4VA / line
Frequency50/ 60Hz
Precision0.2%(U,I); 0.5% (F: 0.05Hz, kVarh: 1%)
Thermal drift<200ppm
RS485 interface2 cables RS485 (Modbus-RTU protocol)
Energy Impulse2 impulse (open-collector) for kWh & kvarh
VCC<48V, Iz<50mA
Constant: 400~3200imp/kWh(/kvarh)
Width of pulse: 80ms±20ms
InstallationStandard 35mm DIN rail
StandardEN61036; EN50022
Isolation2kVAC/min ( input / output / power supply)
input / housing and output / housing >50Mohm
EnvironmentWork Temperature: -20C ~ +55C
Storage Temperature: -40C ~ +70C
Relative humidity: 5% ~ 95% (no condensation)
Altitude: < 2500m
Dimension: 126×89×74 (mm)
Weight: 950g

Three Phase Multi Tariff Watthour Meter (RS485) suppliers    Three Phase Multi Tariff Watthour Meter (RS485) manufacturers