1.Input signals: RTD,ohm,TC,mV
2.Galvanic isolation
3.2-wire technology,4 to 20 mA output
4.Fault signal on sensor break
Port: Xi'an,Shanghai
Minimum Order Quantity: 1 Piece/Pieces
Supply Ability: 500 Piece/Pieces per Week
Payment Terms: T/T,100%TT in advance
Contact SupplierPackaging Detail: standard export package
Delivery Detail: During 7 days after payment received
Detail Product Information
Universally PC programmable
Galvanic isolation
2 wire technology, 4 to 20 mA analog output
High accuracy
Fault signal function
Output simulation
Primary Technical Characteristics
Programmable ...............MS181 programming tool
Measuring range ............Set via PC
PC Interface................... USB/RS232
Input type .......................RTD,TC,R or Millvolt signal
Convert accuracy........... ≤0.1%FS
Cold junction accuracy........... ±1°C(TC)
Output ....................................4~20mA
Max-load ...............................(V -8V)/0.025A(Current output)
Limit current ..........................≤25mA
Response time .......................1s
Isolated Voltage .....................1500V AC(input/output)
Alarm signal ............................Programmable
Below the measuring Output drops to 3.8mA
Higher than the measuring range Output rises to 20.5mA
Sensor faults Setting as≤3.6mA or ≥21.0mA
Power supply ..........................8….35vDC
Temperature drift ....................0.01% FS /1°C
Long-term stability ..................≤0.1°C per year or 0.05% per year
Ambient................................... -40~+85°C