HV phase tester
1.wireless transmission
2.safe, reliable, fast and accurate
3.adapt to a variety of phase testing occasions
Port: wuhan/shanghai
Minimum Order Quantity: 1 Set/Sets
Supply Ability: 50 Set/Sets per Day
Payment Terms: L/C,T/T,Western Union
Contact SupplierPackaging Detail: wooden case
Delivery Detail: 20 days after everything be confirmed
HV phase tester, phasing device, wireless phasing tester, HV phasing tester, phonetic phasing tester
TAG-8000 Wireless HV phasing tester, used in power lines, phase tests and phase sequence tests for substations, with functions of phase testing, phase sequence testing, electrical inspection. With strong anti-interference ability, in line with (EMC ) standards, adapt to a variety of electromagnetic interference occasions. High voltage phase signal will be taken out by the collector, discharge directly after treatment. Received by instrument and compare the phase, and identify the results. This product is wireless transmission, safe, reliable, fast and accurate, adapt to a variety of phase testing occasions.
Its main advantage is without the wire which connect two grids (power source) , distance up to 200M and could trough enclosure or partition plate, improve the safety, without the limitation by terrain and the structure of the equipment , easy to operate, only need one person to operate and one person to supervise.
Products features
1. Use high capacitive non-maintenance lithium battery to supply power, special for field test.
2. Long transmission distance, up to 200M.
3.LCD display phase ,waveform, frequency , safe and reliable.
4. Telescopic insulation bar, easy to use.
5. Portable receiver with non-skid treatment.
6. uses advanced technique, small in volume, light in weight
Products parameters
1. Electrical Specifications
1.1 measurement voltage range: 0.4 ~ 500kV
1.2 wireless transmission distance ≥ 200M
1.3 in-phase definition :strictly according national standard, phase angle ≤30° is in-phase, phase angle≥30° is opposite phase
1.4 working frequency: 45~60Hz, applies to foreign countries 60Hz grid.
2. Insulation parameters
2.1 Launcher (2) insulation grade: 80kV/cm
2.2 Telescopic insulation rod is damp-proof, high voltage resistant, impact resistant, buckling resistant, details see below tables.
Table 1 insulation rod mechanical , electrical parameters
Item | Unit | Index |
Martin heart resistance (portrait) | °C | >200 |
Impact resistance (portrait) | MPa/cm | >147 |
Buckling resistance (portrait) | MPa | >343 |
Surface resistivity (after water-immersed) | Ω | >10x1011 |
Volume resistivity (normal) | Ω/cm | >10x1031 |
Table 2 voltage withstand measurement parameters for insulation rod
Voltage (kV) | Length (m) | Frequency voltage (kV) | Time (min) | Results | |
Standard value | Measurement value | ||||
6-10 | 1.5 | 44 | 44 | 1~5 | Q |
35 | 2.4 | 80 | 80 | 1~5 | Q |
66~110 | 2.8 | 254 | 254 | 1~5 | Q |