1)Settings with HART-protocol
2)Fault signal alarm
3)Galvanic isolation
4) Wide measuring range
5) universal input
Minimum Order Quantity: 1 Unit/Units
Supply Ability: 1000 Unit/Units per Month
Payment Terms: T/T
Contact SupplierPackaging Detail: standard
Delivery Detail: within 2 weeks after payment received
Smart &HART temperature head converter MS182
Description
Technical Characteristics
Programmable.........Use PC or the hand operator
Cold junction accuracy....... ±1°C(TC)
Max-load........(V -13V)/0.025A(Current output )
Limit current....... ≤25mA
Response time.....1s
Alarm signal..........Programmable
Underranging linear drop to 3.8 mA
Overranging linear rise to 20.5 mA
Sensor break or short-circuit: ≤3.6mA or ≥21.0mA
Long-term stability.......≤0.1°C per year or 0.05 %per year
Field of application
Temperature head transmitter with HART® -protocol for converting various input signals into a standard 4 to 20 mA analog output signal
Input:
-Resistance thermometer (RTD)
-Thermocouple (TC)
-Resistance transmitter (Ohm)
-Voltage transmitter (mV)
HART® -protocol for front end unit or panel unit operation using the hand operating
module (MS275, MS375,PDAN800,PDA S900) or PC
Electrical connection
Wiring
Demension