1.1x dry contact output
2.6 LED indicator lights
3.RS485 communication interface
Minimum Order Quantity: 50 Piece/Pieces
Supply Ability: 3000 Piece/Pieces per Month
Payment Terms: T/T,Paypal
Contact Supplier
Gas detected | VOCs ( toluene emitted from wood finishing and construction products); Cigarette smoke( hydrogen, carbon monoxide); ammonia and H2S, alcohol, natural gas and smell by peoples body. |
Sensing element | Semiconductor mix gas sensor |
Power Supply | 18~38VAC/VDC or 220/240VAC (Selectable in orders) |
Consumption | 2.5 W |
Load (for the analog output) | >5K |
Sensor query frequency | Every 1s |
Warm up time | 48 hours (first time) 1 hour(operational) |
Six indicator lights | The first green indicator lightBest air quality The first and the second green indicator lightsBetter air quality The first yellow indicator lightGood air quality The first and the second yellow indicator lightsPoor air quality The first red indicator lightPoorer air quality The first and the second indicator lightsPoorest air quality |
Analog output | 010VDC linear zed output |
Output resolution | 10Bit |
Relay output | One dry contact output, rated switching current 2A( resistance load) |
Communication rate | RS485, 9600/14400/1920(default), 28800, 38400 bps (programmable selection), 15KV antistatic protection, 3 independent base address, 64 max network nodes |
Operation temperature | 050 (32122) |
Operation humidity | 095%RH,non condensing |
Storage conditions | -4070 (-40158) |
Weight | 190g |
Dimensions | 100mm×80mm×28mm |
Installation standard | 65mm×65mm or 2×4wire box |
Wiring terminals | Maximum 7 terminals |
Housing | PC/ABS Plastic fireproof material , IP30 protection class |
Quality standard | ISO 9001 |
1) Wall mounting, VOC detector is used to real time detect room VOC level
2) With Japanese famous semiconductor mix gas sensor, 5~7 years lifetime.
3) The sensor is sensitive to VOC such as various kinds of odorous gases and combustion gas in the room (smoke, CO, alcohol, human odor, material odor).
4) With 6 LED indicator lights to indicate different IAQ levels.
5) One on/off output optional with four IAQ ranges selectable to control the relay output. A touch button on the cover to switch Fan On/Fan Off/Auto Fan
6) 24VAC/VDC power supply or 230VAC power supply with a power adaptor