Temperature head transmitter
1)Settings with HART-protocol
2)Galvanic isolation
3)RTD,TC,R,Ohm input
4)4to20mA output
Minimum Order Quantity: 1 Unit/Units
Supply Ability: 1000 Unit/Units per Month
Payment Terms: T/T
Contact SupplierPackaging Detail: Standard export package
Delivery Detail: within 2 weeks after payment received
Performance
Technical characteristics
Programmable........Use PC or the hand operator.....
Measuring range.........Set via PC or by the hand operator
Input type ...................RTD, TC, R or Millivolt signal
Convert accuracy.........≤0.1%FS
Cold junction accuracy ......±1°C(TC)
Output...................4~20mA/20~4mA Electrical isolation output
HART –Protocol output
Max-load...............(V -13V)/0.025A(Current output )
Limit current.............≤25mA
Response time............1s
Isolated voltage...........1500V AC (input/output)
Alarm signal.................Programmable
Underranging linear drop to 3.8 mA
Overranging linear rise to 20.5 mA
Sensor break or short-circuit:≤3.6mA or ≥21.0mA
Power supply...............13~30V DC
Temperature drift...........0.01% FS/1°C
Long-term stability..........≤0.1°C per year or 0.05 %per year
Ambient..........-40~+85°C
Field of application
Temperature head transmitter with HART® -protocol for converting various input signals into a standard 4 to 20 mA analog output signal
Input:RTD,TC,Ohm,mV
HART® -protocol for front end unit or panel unit operation using the hand operating module(MS275, MS375,PDAN800,PDA S900) or PC
Electrical connection