Home  >  Electrical Instruments  >  Power Meters

PMAC720 Digital Energy Meter - PMAC720

PMAC720 Digital Energy Meter, 1. Power metering: U,I,P,Q,kWh, 2. RS485/ Modbus, 3. Optional DI/ DO module, 4. Harmonic analy - more info check here: http://www.buymeasuringtools.com/PMAC720-Digital-Energy-Meter-10055780/

Quick Brief

Place of Origin: Guangdong China (Mainland) Brand Name: Pilot Model Number: PMAC720 Measuring Current Range: 0~49,999A Measuring Voltage Range: 0~220KV Accuracy Class: 0.2% Operating Temperature: -20~+60 Dimensions: 96x96mm Metering: True RMS, 1 sec. refresh time Current input: 1A or 5A Voltage input: 220V/ 380V or 57.7V/ 100V Frequency: 50 or 60Hz Over load: 120% of rating Power supply: 85~265VAC or 80~300VDC IP index: IP54 (front panel), IP20 ( case) Net weight: 500g Certificate: CE Standard: IEC 61000-4-2/3/4/5

Product Features:

PMAC720 Digital Energy Meter

1. Power metering: U,I,P,Q,kWh

2. RS485/ Modbus

3. Optional DI/ DO module

4. Harmonic analy

Business Terms:

Port: Zhuhai

Minimum Order Quantity: 32 Piece/Pieces samples is also welcome

Supply Ability: 3000 Piece/Pieces per Month

Payment Terms: L/C,T/T,Western Union

Contact Supplier
PMAC720 Digital Energy Meter
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: 8pcs/carton

Delivery Detail: 7 days

Specifications and Product Details:

PMAC720E Digital Energy Meter

Feature:

1. Suit for LV/ HV voltage system

2. Compact design with all real-time measurement

3. Consist of basic unit and optional modules

4. 10 years back-up of integrated energy data

5. Large LCD, high brightness, auto-scrolling

6. High accuracy, V or I is 0.2%, kWh is class 1

7. CT and PT programmable

8. Pluggable terminals, easy to install

9. Panel size: 96 x 96mm

10. Password protect

Basic Function:

Provide one RS485 communication, measures and display real-time parameters:

1. Voltage—Ua, Ub, Uc, Uab, Ubc, Uca,

2. Current—Ia, Ib, Ic, In

3. Active power – Pa, Pb, Pc, ∑P

4. Reactive power –Qa, Qb, Qc, ∑Q

5. Power factor—PFa, PFb, PFc, ∑PF

6. Frequency

7. Active energy—kWh

8. Reactive energy– kvarh

Optional Modules:

1. 4 status input (dry contact) + 4 relay output

2. 8 status input (dry contact) + 2 relay output

3. 4 status input (wet contact) + 4 relay output

4. 8 status input (wet contact) + 2 pulse output

5. 2 pulse output + 2 analog output

Optional Function:

1.Up to 31st harmonic analysis, K factor, THD

2. SOE (event log)

3. TOU (multi-tariff)

4. One 4~20mA analog input

5. One 4~20mA analog output

Accuracy:

ParameterAccuracyResolutionMeasuring range
Voltage0.2%0.01direct 520V ph-ph

PT primary; 0~999999V

Current0.2%0.0010~49999A
Power0.5%0.10~100MW/ Mvar
Power factor0.5%0.001-1.000~+1.000
Frequency0.010.0145~65Hz
Active energy1.0%0.10~99,999,999.9kWh
Reactive energy2.0%0.10~99,999,999.9 kvarh
Individual harmonic1.0%0.0010~100%
Un-balance1.0%0.0010~100%