1. Based on metal capacitive technology;
2. Instrasic safety(Exia IICT6), flame-proof Exd IICT6)optional.
Port: Xian
Minimum Order Quantity: 1 Piece/Pieces
Supply Ability: 5000 Piece/Pieces per Month
Payment Terms: L/C,D/A,D/P,T/T,Western Union,MoneyGram
Contact SupplierPackaging Detail: each unit has individual box and all boxes are packed in standard packages.
Delivery Detail: in 5 days
Based on metal capacitive technology, UPB1151 series differential pressure transmitters is designed by using selected high accuracy & stability electric capacitive sensor, that use one-side or two-side stainless steel or tantalum isolated diaphragm. After strict temperature compensation, linearity compensation, signal amplified, V/I transforming, antipolarity protection, pressure overload, and current limiting processing, the parameters like differential pressure, gauge pressure, fluid, and level can be transformed to standard signal of 4~20mA or 0~20mA by UIB1151.
UPB1151 series metal electric capacitive pressure transmitters can be connected with Process Automation Instrumentation or computer control system, realizing precise measurement for corrosive gas pressure, liquid pressure, steam pressure, level or fluids etc. UPB1151 series metal capacitive pressure transmitter is widely used in technical areas such as petroleum industry, chemical industry, steel and iron industry, electric power, food, papermaking industry, spinning and weaving, medicine and environmental protection and so on.
Features:
*Excellent measuring performance, suitable for measurement of differential pressure, gauge pressure, absolute pressure and level.
*Wide range shift, can be shifted downwards or upwards.
*Have adjustable damping device, can measure pulsation fluids.
*Instrasic safety(Exia IICT6), flame-proof Exd IICT6)optional.
*Protection:IP67
Speifications
pressure medium | gas liquid and steam |
pressure ranges | 0~0.1kPa...10MPa D 0~1kPa...40MPa G 0~6kPa...10MPa A |
pressure type | gauge(G),absolute(A),differential (D) |
system pressure | 40bar/100bar/250bar/320bar |
output signal | 4~20mA |
accuracy | 0.1%FS , 0.2%FS, 0.5%FS |
system pressure effect | 0.2%FS/10MPa(can be modified under pipeline) |
load resistance | RL= (U-12V)/0.02A U-power supply voltage (V DC) |
long term stability | not exceed absolute value of max. range’s basic error in 12 months |
supply voltage | 12~45V |
operating temperature range | -40~+85°c, (-20~+65°c with indicator) |
media temperature range | -40~+120°c |
storage temperature range | -40~+105°c |
temperature coefficient of zero | 0.03%FS/10°c |
temperature coefficient of span | 0.03%FS/10°c |
insulation resistance | 100MΩ @ 50VDC |
process connection | 1/4"NPT |
electrical connection | M20×1.5 or 1/2NPT |
meter | 0~100% linear meter ot 3-1/2 digital meter |
sensor filled oil | silicon oil, fluorocarbon oil |
o-ring | butyronitrile rubber, fluorine rubber, polytetrafluoro, metal sealing ring etc |
Electronic shell and coating | low copper aluminum alloy, anodic oxidation, spray coating polyurethane |
Electromagnetic/radio-frequency interference influence | 20~1000MHz,output shift<0.01%FS for Field intensity of 30V/m |
Vibration influence | on any axial,0.05%FS/g under 200Hz |
Protection | IP67 |