Loop Calibrator YH7007
1,We can provide OEM Service
2,Prompt delivery
3,Max voltage -30V
4,LCD display
Port: Shenzhen
Minimum Order Quantity: 1 Piece/Pieces Price can be negotiable according to your quantity
Supply Ability: 5000 Piece/Pieces per Month More can be provided according to customers; need
Payment Terms: T/T,Western Union,MoneyGram
Contact SupplierPackaging Detail: gift box for unit ,carton box for outer
Delivery Detail: Within one month after receiving the deposit
Loop Calibrator YH7007 +Selectable slow ramp, fast ramp, and step ramp to provide smooth outputs for valve
We can provide OEM Service for customers completely
Features
The fast, one-handed tool for loop checks. Just click to calibrate.
This feature-rich solution combines the best features push-button and knob-base loop calibrator and offers:
Current Measurement | Range: | 0 to 24 mA |
Resolution: | 0.001 mA | |
Accuracy: | 0.025% Rdg + 2 LSD | |
Current Sourcing | Range: | 0 to 20 mA or 4 to 20 mA |
Accuracy: | 0.025% Rdg + 2 LSD | |
Drive Capability: | 1200 Ω; 950 Ω at 20 mA in HART mode | |
Current Simulation | Range: | 0 to 20 mA or 4 to 20 mA |
Accuracy: | 0.025% Rdg + 2 LSD | |
Ext. loop voltage requirement: | 12-30 V | |
Loop Power | While measuring mA, 24 V | |
Voltage measurement | Range: | 0 to 28 V DC |
Resolution: | 1 mV | |
Accuracy: | 0.025% Rdg + 2 LSD |
Operating Temperature -10ºC to 55ºC
Storage Temperature -30ºC to 60ºC
Humidity (Without Condensation) 0 to 90% (0ºC to 35ºC); 0 to 70% (35ºC to 55ºC)
Temperature Coefficient -10ºC to 18ºC, 28ºC to 55ºC, ±.005% of range per ºC
Maximum voltage 30V
Mechanical & General Specifications
Size 152 x 70 x 41 mm
Weight 224 g (340 g including holster)
Batteries One 9V battery Alkaline(YHS-707) , One 9V battery
Warranty Two years
Shock & Vibration per MIL-T-28800 for a Class 2 Instrument
Display current and % of span Yes
Auto step, auto ramp Yes
Span Check Yes