1.Programmable PT (1 to 3000) Ratios
2.Large Dot Matrix LCD Display with Backlight
3.Built-in Calendar Clock for Data Logging
Port: shenzhen or guangzhou
Minimum Order Quantity: 10 Piece/Pieces
Supply Ability: 10000 Piece/Pieces per Day
Payment Terms: T/T,Western Union
Contact SupplierPackaging Detail: 1pc/colorbox
Delivery Detail: 3-5days
Feature:
•Display of Overlapped Voltage and Current Waveform
•Maximum Demand (MD in W, KW, MW) with Programmable Period
•Harmonics Analysis ( V and I ) to the 50th Order
•Display of 25 Harmonics in One Screen with Waveform
•Display of waveform with Peak Values (512 Samples / Period), Datalogging of 32, 64, 128 or 256 Points/Cycles
•Analysis of Total Harmonics Distortion ( % THD-F )
•Graphic Phasor Diagram
•Capture 128 Transient Events ( Time + Cycles + Faults ) with Programmable Threshold(%), Can Also be Reviewed in LCD
•50000 Records with Programmable Interval ( 1 to 6000 seconds)
•Output of Waveform, Power Parameters and 50 Harmonics at Command.
•Optical Isolated RS-232C Interface
•Smart Datalogging to save Battery Power for Long-term Monitoring
Specification:
AC Watt ( 45 ~ 65 Hz, PF 0.5 to 1, CT=1 )
Range | Resolution | Accuracy of Readings |
100.0 - 999.9 W | 0.1 W | 2% ± 8 dgts |
1.000 - 9.999 KW | 0.001 KW | 2% ± 8 dgts |
10.00 - 99.99 KW | 0.01 KW | 2% ± 8 dgts |
100.0 - 999.9 KW | 0.1 KW | 2% ± 8 dgts |
1000 - 9999KW | 1 KW | 2% ± 8 dgts |
AC Current (45~65 Hz , True RMS)
Range | Range | Resolution | Accuracy of Readings |
30 - 300 A | 0.00 - 300 A | 0.1 A | 1 % of range ± 8 dgts |
300 - 999.9 A | 100.0 - 999.9 A | 0.1 A | 1 % of range ± 8 dgts |
1000 - 3000 A | 1000 - 3000 A | 1 A | 1 % of range ± 8 dgts |
Harmonics of ACA in % and Magnitude (1 to 50th order)
Range | Resolution | Accuracy in % | Resolution | Accuracy in Magnitude |
10.0 - 300 A | 0.1 % | ±1.0% | 0.1 A | ±1.0% of range ± 0.8A |
1000 - 3000 A | 0.1 % | ±1.0% | 1 A | ±1.0% of range ± 3 A |
Power Factor (PF)
Range | Resolution | Accuracy of Readings |
0.00 - 1.00 | 0.01 | ± 1.5 % ± 8 digits |
Harmonics of AC Voltage in % and Magnitude (1 to 50th order)
Range | Resolution | Accuracy in % | Resolution | Accuracy in Magnitude |
50 - 600 V | 0.1 % | ±0.5% | 0.1V | ±0.5 % ± 0.5V |
Phase Angle ( Φ )
Range | Resolution | Accuracy of Readings |
-180 ° to 180 ° (0 ° to 360 ° ) | 0.1 ° | ± 1 % ± 2 digits |
AC Voltage ( 45 ~ 65 Hz, True RMS)
Range | Resolution | Accuracy of Readings |
3 V - 600 V | 0.1 V | ± 0.5 % ± 5 dgts |
Total Harmonics Distortion (% THD-F , 1 to 50th order)
Range | Resolution | Accuracy of Readings |
0.0 - 999.9 % | 0.1 % | ± 0.5 % ± 5 digits |
General Specification:
Conductor Size | 150 mm (approx.) |
Battery Type | 1.5 V SUM-3 *2 |
Display | 128*64 Dot Matrix |
Power Consumption | 10 mA (approx.) |
Auto - Power - Off | 15 minutes |
LCD update rate | 2 times/sec |
Dimension | 130mm(L)*80mm(W)*43mm(H), 5.1"(L)*3.1"(W)*1.7"(H) |
Accessories | Test lead*1 pair, Users manual*1, Batteries 1.5V*2 |
No. of Sample / Period | 512 ( V & A ), 256 (W) |
Operating Temperature | -10 °C to 50 °C |
Operating Humidity | < 85% RH |
Storage Temperature | -20 °C to 60 °C |
Storage Humidity | < 75 % RH |
Weight | 450g |