1.25m range, 2 inch dead band
1 inch NPT mount
Outputs for full pump or valve control
PVDF transducer for corrosive liquid
Minimum Order Quantity: 1 Set/Sets
Payment Terms: T/T
Contact Supplier
Range: 1.25 m
Accuracy: 3 mm
Resolution: 0.5 mm
Beam Width:5 cm
Dead Band: 5 cm
Supply Voltage: 24VDC (loop)
Loop Resistance: 400Ω max.
Consumption: 0.5W
Signal Output: 4-20 mA, two-wire (when loop powered)
Contact Type: (4) SPST relays 1A
Loop Fail-Safety: 4 mA, 20 mA, 21 mA, 22 mA or hold last
Relay Fail-Safety Power loss: Hold last; Power on: Open, close or hold last
Hysteresis Selectable
Configuration Software PC Windows® USB 2.0
Temp. Comp: Automatic over range
Process Temp: 20°F to 140°F (-7°C to +60°C)
Ambient Temp: -31°F to +140°F (-35°C to +60°C)
Pressure: MWP = 30 PSI
Enclosure Type: 6P encapsulated, corrosion resistant & submersible
Encl. Material: PC/ABS FR
Strain: Relief Mat. Santoprene®
Trans: Material PVDF
Cable Length: 1.2 m
Cable Jacket: Mat. Polyurethane
Mount: Gasket Viton®
Classification: General Purpose
Approvals: CE, cFMus