Home  >  Temperature Instruments

Field RTD Input Temperature Transmitter with Galvanic isolation MS190 - MS190

1.Input type:RTD, TC, R or mV, 2.With HART Protocol, 3.Digital display (LED,LCD), 4.2 wire technology, 4 to20ma output - more info check here: http://www.buymeasuringtools.com/Field-RTD-Input-Temperature-Transmitter-with-Galvanic-isolation-MS190-10171312/

Quick Brief

Place of Origin: Shaanxi China (Mainland) Brand Name: Moshu Group Model Number: MS190 Usage: Industrial Theory: Temperature Transmitter HART Protocol: Yes Explosion-proof class: Exdii CT6 EX ia iiCT6 Measuring range: Programmable Digital display: LED,LCD

Product Features:

1.Input type:RTD, TC, R or mV

2.With HART Protocol

3.Digital display (LED,LCD)

4.2 wire technology, 4 to20ma output

Business Terms:

Port: Xi'an

Minimum Order Quantity: 1 Piece/Pieces

Supply Ability: 500 Piece/Pieces per Week

Payment Terms: 100%TT in advance

Contact Supplier
Field RTD Input Temperature Transmitter with Galvanic isolation MS190
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: standard export package

Delivery Detail: During 7 days after payment received

Specifications and Product Details:

MS190 Temperature Transmitter

Detail Product Information

Primary Technical Characteristics

Programmable .............................Use PC or the hand operator

Measuring range .........................Set via PC with special interface or by the hand operator

Input type.................................... RTD, TC, R or Millvolt signal

Convert accuracy .......................≤0.1%FS

Cold junction accuracy............... ±1°C(TC)

Output......................................... 4~20mA/20~4mA Electrical isolation output HART Protocol output

Max-load.................................... (V -13V)/0.025A(output Current)

Limit current ...............................≤25mA

Response time ............................1s

Isolated voltage ...........................1500V AC (input/output)

Alarm signal................................. Programmable

Below the measuring range Output drops to 3.8mA

Higher than the measuring range Output rises to 20. 5mA

Sensor faults Setting as≤3.6mA or ≥21.0mA

Power supply ..............................13~30V DC

Temperature drift ........................0.01% FS / 1°C

Long-term stability ......................≤0.1°C per year or 0.05% per year

Protection level............................IP67(aluminum alloy),IP65(plastic)

Digital display............................. LED,LCD

Display voltage-drop ..................3V(LED),0.5V(LCD)

Display accuracy ........................0.1%

Ambient..................................... -40~+85°C

Explosion-proof class................. Exdii CT6 EX iaii CT6

Field of application

PC programmable (PCP) Field-mounted temperature transmitter for converting various input signals into a standard 4 to 20 mA analog output signal

Input:

Resistance thermometer (RTD)

Thermocouple (TC)

Resistance transmitter (Ohm)

Voltage transmitter (mV)

HART-protocol for front end unit or panel unit operation using the hand operating module (MS275, MS375,PDA N800,PDA S900) or PC

Every part is coming from Moshu Group! From professional factory!

Field RTD Input Temperature Transmitter with Galvanic isolation MS190 suppliers    Field RTD Input Temperature Transmitter with Galvanic isolation MS190 manufacturers