1.highest working voltage: DC 220V or AC 380V
2.contact power: 10VA
3. work position: upright install
Port: Shanghai Port
Minimum Order Quantity: 1 Unit/Units
Supply Ability: 1000 Unit/Units per Week
Payment Terms: T/T,Western Union
Contact SupplierPackaging Detail: paper box
Delivery Detail: in5-15working days
Explosion-proof electric connect point pressure meter
Explosion-proof electric connect point pressure meter is designed based on the prescribe and the standard of GB3836.1 83(the currency request of using explosion-proof electric equipment in explosion-proof environment) and GB3836.2 83(use explosion-proof equipment flameproof electrical apparatus in the explosion-proof environment “d”). And produce based on the picture and technology which is agreed by the country appointed checking organization.
The explosion-proof class of the instrument is 2 flameproof B class T4 group, its sign is Exd2 BT4.
The instrument is used to measure the pressure of the no crystallization, no solidification explosion mixture or other no volatile medium in the explosion hazard environment.
Instrument can reach the purpose of automatic control and set a signal(alarm) after equipped with the electric devices which has the explosion-proof capability or adopt correspond safety method.
Main technical parameter:
Accuracy 1.5
scaling range 0~0.16 0~0.2, 0~0.4, 0~0.6, 0~1, 0~1.6, 0~2.5, 0~4, 0~6, 0~10, 0~16,0~25 0~40,0~60, -0.1~0.06, -0.1~0.15 -0.1~0.3 ,-0.1~0.5, -0.1~0.9 -0.1~1.5, -0.1~2.4MPa
control method top and low limit amble reed switch.
highest working voltage DC 220V or AC 380V
contact power 10VA
work position upright install
usage environment condition -10~50°C, relative humidity is not more than 80%, and explosion mixture is lower than 2B class T4 group, working libration and the rapid pulsate of the measuring medium has no influence on the credibility action of the instrument contact.
temperature influence value is not more than 0.4%/10°C, setting point is not more than 0.6%/10°C( usage temperature departure 20±5°C).
insulated intension 50Hz sinus alternating current 2000V need a minute.
weight 6kg
Flameproof joint type and basic parameter
Shell cubage V(L) | >0.5 | ||
Joint plate type | plane | Cylinder(the moving part) | |
Least action length of the flameproof joint Lmm | 15 | ||
Least action length of the bolt blowhole edge to flameproof joint L1 | 8 | ||
Maximum clearance or diameter difference of the flameproof joint Wmm | 0.15 | ||
Surface roughness of the flameproof joint Ra | 3.2 | 1.6 | |
Note: the action length and the clearance width of the flameproof joint’s example can see to flameproof enclosure structure figured diagram.
· the accessory and material of the flameproof enclosure and lead pressure
Part name | Material trademark or name | Accessory name | Material trademark or name |
Drive shell annex Outlet box | ZL102 (or ZL-102,ZL-101) | Thin gasket | L3 |
connector | 20 | ||
Shaft linear | QAJ9-2 | Spring pipe | 3J53 |
Sight flow glass | Organic glass |
Note: the material of the sight flow glass’s resist impact strength is not smaller than 4J. sight flow
glass will not be used if it is mangel.
Configuration theory
Instrument consist of flameproof enclosure, measuring system, electric connect point group, adjust
device and outlet box etc. the flameproof enclosure of the instrument has good flameproof capability, so at the normal working process, it can bear the explosion pressure that is arosed by the explosion gas mixture inside, and also can prevent the heat energy to spread, only can spread in the minim aperture of the flameproof joint because of the function of the light and electric-arc. At this time, the temperature is lower than flameproof gas mixture’s burning point, so it will not cause explosion.
Instrument’s working principle base on the elasticity distortion of the detecting element(spring pipe of the measuring system), and reach the purpose of the automatic control alarm and locale indicator by the mechanical drive to drive the contact of the electric connect point group to bring correspond action( close or opening).