Digital insulation multimeter YH5110
insulation tester+insulation multimeter
OEM Service provided
50000 counts measurement
Port: Shenzhen
Minimum Order Quantity: 10 Piece/Pieces Price can be negotiable
Supply Ability: 10000 Piece/Pieces per Month More can be provided according to customers' need
Payment Terms: T/T,Western Union,MoneyGram
Contact SupplierPackaging Detail: gift box for unit ,carton box for outer
Delivery Detail: 5-7days
Digital insulation multimeter-YH5110
Specifications
Complies with IEC/EN 61010-1 1000V CAT III ,600 V CAT IV.
1000V DC Voltage,750V AC Voltage(TRMS).
6600 Count(except for capacitance,temperature,insulation).
When the input terminals is V and COM,The overload protective voltage is up to AC 250 V (TRMS) ;When the input terminals is mA and COM, protective Current is 0.4A; when the input terminals is Hi and Lo , The overload protective voltage is 600V.
Batteries:Four AA batteries (NEDA 15A or IEC LR6) Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Insulation Measurement Range : 0.01 MΩ to 2 GΩ.
Insulation Test Voltages : 50, 100, 250, 500, 1000 V .
Insulation Source Voltage: + 20 %, - 0 %.
Insulation Short-Circuit Test Current : 1 .5mA nominal.
Insulation Auto Discharge : Discharge time <1 second for C = 1 μF or less.
Insulation Live Circuit Detection : Inhibit test if terminal voltage > 20 V prior to initialization of test.
Insulation Maximum Capacitive Load: Operable with up to 1 μF load.
Storage Temperature : -40 °C to 60 °C.
Operating Temperature: 0°C to 40 °C .
Storage Altitude: 12000m
Operating Altitude: 2000m 1000V CAT III,3000m 1000V
Temperature Coefficient: 0.05 × (specified accuracy) per °C for temperatures < 18 °C or > 28 °C.
Relative Humidity: 40%~75%.
lSize: 205(L)×102(W)× 58(H)mm.
Weight: approx 390g.