Digital Process Temperature Controller
SUMMARY
1.1 Main feature
Advanced operation method leads to easy learning and simple manipulation; and the compatibility of operation is available among the instruments differ in the model and function.
Provide nearly all of the functions contained by most similar industry automatic controller in the world, and the mature technique made it generally used in various kinds of industrial fields.
Provide various models that can meet different needs either in the functions or price.
With power supply of 85-264VAC or 24VDC and various installation dimensions for users to choose.
Adopt digital calibration system for measurement input with measurement input accuracy less then 0.2% F.S., non-linear calibration for common sensors is available in the instrument.
Adopt advanced Temperature Controller artificial intelligence control algorithm, no overshoot and with the function of auto tuning and self-adaptation.
Adopt advanced modular structure, equipped with plentiful output specifications, and can satisfy the needs of various applications. This makes it possible to shorten the date of delivery and convenience the maintenance of the instrument.
Specification's for temperature controller:
- Input type: (Either of below specifications can be used selectively in the same instrument)
- Thermocouple: K, S, E, R, J, T, B, N
- Resistance temperature Detector: PT100, Cu50
- DC Voltage: 0_5V, 1_5V, 0_1V, 0_100mV, 0_20mV, etc.
- DC current (external shunt resist needed): 0_10mA, 1_20mA, 4_20mA, etc.
- Optional: Apart from the above-mentioned Input type, additional type can be provided upon request.
- Instrument Input range
K(-50--+1300C), S(-50--+1700C), R(-50--+1650C), T(-200--+350C),
E(0_ 800C), J(0--1000C), B(0--1800C), N(0_ 1300C).
PT100(-200--+600C), Cu50(-50--+150C).
Linear Input: -1999--+9999 defined by user. - Measurement accuracy
0.2%FS: RTD, linear voltage, linear current and input with ice point compensation or Cu50 copper Compensation. - 0.2%FS± 0.2C: Thermocouple input with internal automatic compensation.
- Response time ≤ 0.5s ( when dL=0). Note: For thermocouple B, the measurement accuracy of plusmn; 0.2% FS can be guaranteed when input
Range is between 600--1800C, and not guaranteed when input range is between 0--600C. - Control mode:
On-off control mode (deadband adjustable)
Intelligence control, including fuzzy logic PID control and advanced control algorithm with
The function of parameter auto tuning (MPT). - Output mode (modular)
Relay contact discrete output (NO+NC): 264VAC/1A or 30VDC/1A
BCR NO contact discrete output (NO+NC): 85_ 264VAC/0.2A (continuous), 2A (20mS
Instantaneous, repeat period≥ 5s) - SSR Voltage output: 12VDC/30mA (used to drive SSR).
- Linear current output: 0_ 10mA, 4_ 20mA (Output voltage greater than 11V)
Parameter Setting Flow Chart:
Program Setup Flow chart:
FRONT PANEL AND OPERATION
Details photo of temperature controller