1.easy operating,auto-tuning
2.economical temperature controller
3.stable performance
4.fuzzy control
5.PID control
Port: Shanghai
Minimum Order Quantity: 1 Piece/Pieces
Supply Ability: 10000 Piece/Pieces per Month 1
Payment Terms: T/T
Contact SupplierPackaging Detail: box
Delivery Detail: 1day
1. INTRODUCTION.
2. TECHNICAL SPECIFICATION OF TEMPERATURE CONTROLLER .
Input type: RTD
Measurement range : Pt100 (-200~600 degree C )
Measurement accuracy: 0.3%FS±1 degree C
Temperature display resolution: 1/0.1 degree C.
Control mode: On-off control mode or Artificial Intelligence control with auto tuning.
Output mode (modularized) : SSR.
Alarm function: High limit and deviation high alarm.
Power supply voltage rating: 100-240VAC, -15%, +10%; 50-60Hz.
Power consumption: ≤5W.
Ambient : Temperature -10~60 degre C , Relative humidity of 0~90RH%.
Practical Consideration before running an Auto-Tune
Note 1: Before running auto-tuning, set point should be set to an often-used value or if not, set to a middle value befor einitiate an auto-tuning. Generally, for application with 10%~80% time on heating can obtain satisfying auto-tuning result. If the heating time is not in the range of 10~80%, the auto-tuning will run for a long time and can’t get satisfying result. Raising set point for heating time less than 10% or decreasing set point for heating time greater than 80% can improve auto-tuning result
Note 2: Don't modify the set point during auto-tuning. It may affect the precision of auto-tuning
Note 3: After auto-tuning finishes, generally, the temperature rising has a little over-shoot (about 1~3°C). It is because considering that the transducer is often placed between the heater and heated material, and a little over-shoot can shorten the time of rising to set point and save Power. (Generally, the temperature of transducer can be raised quickly than that of heated material)
3. FRONT PANEL AND OPERATION
Basal display status: When power on, the upper display window of the instrument shows the process value (PV), and the lower window shows the set point (SV). This status is called basal display status. When the input signal is out of the measurable range (for example, the thermocouple or RTD circuit is break, or input specification sets wrong), the upper display window will alternately display “orAL” and the high limit or the low limit of PV, and the instrument will automatically stop output.
Details photo of temperature controller :