Home  >  Testing Equipment

DZ603-6 Energy Meter Calibration Test Bench - DZ603-6

1. 15years professional manufacturer, 2.Certificate: ISO 9001;, 3.Accuracy class: 0.05, 0.1;, 4.Excellent aftersale service - more info check here: http://www.buymeasuringtools.com/DZ603-6-Energy-Meter-Calibration-Test-Bench-10213087/

Quick Brief

Place of Origin: Henan China (Mainland) Brand Name: SMS Model Number: DZ603-6 Power: Electronic

Product Features:

1. 15years professional manufacturer

2.Certificate: ISO 9001;

3.Accuracy class: 0.05, 0.1;

4.Excellent aftersale service

Business Terms:

Port: As per your request

Minimum Order Quantity: 1 Set/Sets

Supply Ability: 10 Set/Sets per Week

Payment Terms: T/T,Western Union

Contact Supplier
DZ603-6 Energy Meter Calibration Test Bench
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: Plywood case

Delivery Detail: 30 days

Specifications and Product Details:

DZ603-6 Energy Meter Calibration Test Bench

Main Performance:

1. Shall carry out completely automatic calibration items such as running with no load, starting, basic error, standard distortion and 24 hours variation etc according to testing regulations: four quadrant: positive, negative, active or reactive error test, automatic shift the input of all kinds of pulse.

2. The tested meters maybe same specification but different communication protocols.

3. Shall carry out tests such as demand cycle and its display, time interval error, register combined error and daily error.

4. Communication test, GPS broadcast time calibration, meter data verification, regarding record meter number.

5. According to regulations, carry out various influence value test, voltage falling and interruptions shall be carried out.

6. Automatically adjust black spot, calculate time for starting test and running with mo load test according to regulations.

7. Shall adopt fixed time and fixed quality burden methods to carry out the reading test, and different time interval with different burden tests are available.

8. Shall display the voltage and current wave diagram with same phase: shall set and measure 2~21 times harmonic wave and measure the distortion degrees.

9. Data be processed and printed automatically, and the table lay out shall be set freely according to user's requirements, transfer data by all M2S port.

10. Support: bar code input, error curve, error limit setting, multi-mode calibration plans and equipment management authority etc.

item

Class 0.1Class0.05

Equipment accuracy class

0.1 for active

0.2for reactive

0.05 for active

0.1 for reactive

Standard meter accuracy class

0.050.02

Voltage isolated transformer accuracy class

0.010.01

Current range

0.1A 0.5A 1.0A 2 .5A 5A 10A 50A 100A

Voltage range

57.7V 100V 220V 380V

Output power

voltage

180VA/phase

Current

240VA/phase

Voltage adjusting

Adjusting range

0~120%

Adjusting resolution

10% 1% 0.1% 0.01% 0.001%

Current adjusting

Adjusting range

0~120%

Adjusting resolution

10% 1% 0.1% 0.01% 0.001%

Phase adjusting

Adjusting range

0.00°~359.99°

Adjusting resolution

10° 1° 0.1° 0.01°

Frequency adjusting

Adjusting range

45.00~65.00Hz

Adjusting resolution

10Hz 1Hz 0.1Hz 0.01Hz

Waveform distortion

<0.5%

Three phase dissymmetry

<0.5°

Power stability

<0.05

Display

Accuracy class

Voltage

±0.3%

Current

±0.3%

power

±0.3%

frequency

± 0,02Hz

phase

<0.2°

Working power

220V±10% 50Hz

Technial Index:

DZ603-6 Energy Meter Calibration Test Bench suppliers    DZ603-6 Energy Meter Calibration Test Bench manufacturers