1.Three phase multifunction din rail energy meter
2.Measure active&reactive power
3.Measure multi-tariff
4.RS485communication
Port: Ningbo
Minimum Order Quantity: 50 Piece/Pieces
Supply Ability: 6000 Piece/Pieces per Week
Payment Terms: T/T,Western Union
Contact SupplierPackaging Detail: white box+ carton
Delivery Detail: about 10 working days
DTSD866 Three phase multi-function din rail energy meter
1.35mm standard DIN rail installation,complying with standard DIN EN50022.
2. Seven module 125mm width.
3. LCD display without backlighting;May select with white backlighting,and there is maintenance free battery used for display
when power-supply cut off.
4. Standard configuration one port of pulse output passive (polarity),may select increase a distant port of pulse output passive
(nonpolarity),complying with standard IEC62053-31 and DIN 43864.
5. LED indicates respectively power-supply,impulse,and communication,etc.
6. Measure power consumption.
7. Measure three phase current.
8. Measure neutral current.
9. Measure equipment temperature.
10.Measure run hour of equipment.
11.Measure three phase voltage,active power,reactive power,power factor.
12.Long term storage for record data.
13.Large LCD screen display,makes the display more visual and easier operation.
14.Communicate data collection via usb flash disk or RS485(Modbus).
15.Data analysis via PC,and automaticly draw out waveform parameter.
16.Through CT or PT & CT.
17.Standard configuration short terminal cover, which is helpful to reduce installation space and make it convenient to install;
May select extended terminal cover.
TECHNICAL PARAMETERS | ||
Accuracy | Class 1.0 | |
Rated voltage(VAC) | 3*220/380, 3*230/400, 3*240/415,etc. | |
Operation voltage range | Un±20% | |
Insulation capabilities | AC voltage withstand 2kV for 1 minute;Impulse voltage withstand 6kV - 1.2/50μs waveform | |
Rated current(A) | 1.5(6) | |
Operation current range | 0.05Ib~ Imax | |
Starting current | 0.004Ib | |
Rated frequency | 50Hz or 60 Hz | |
Interface | optical coupler (SO corresponding to DIN 43864) | |
Impulse valence Ra | 0.5 or 1.0 Wh/imp | |
Max.operation temperature | -40°C ~ +80°C | |
Max.storage temperature | -45°C ~ +85°C | |
Relative humidity | ≤ 85% | |
RS485 communication | Baud rate: 1200bps (default) | |
Remote pulse output | Pulse width: 80ms ± 20ms | |
Service Life | More than 10 years | |
Dimension | 125mm x 88mm x 73mm | |
Weight | Approx 650g |