DC Current Transformer:
1.10(100)A/4mA 20Ohm Class0.1
2.CT with plastic cap
3.higher accuracy
4.MOQ:100pcs
Port: Shanghai Airport/Port
Minimum Order Quantity: 100 Piece/Pieces
Supply Ability: 20,000 Piece/Pieces per Day
Payment Terms: L/C,T/T,Western Union
Contact SupplierPackaging Detail: Cartons
Delivery Detail: Within 10-15days
PQCT-12 current transformer for energy meter specification
current transformer Basic Parameter | Primary current (A) | Secondary current (mA) | Resistance Rb (Ω) | Maximum current(A) | Class | Remark | ||||||||
10 | 4 | 20 | 100 | 0.1 | ||||||||||
Current error and phase error limited | Class | Current error±(%) | Phase error( ) | |||||||||||
0.01In | ≥0.05In | 0.01In | 0.05In | 0.2In | 1In | 2In | 3In | Imax | ||||||
0.1 | 0.2 | 0.1 | 15 | 8 | 5 | 5 | 5 | 5 | 5 | |||||
Note,between the current 0.2In~Imax,taking the average δe between the maximum and minimum phase error. δi=δi-δe.( δI: phase error,δI, phase displacement when the working current at i time,δe,average phase displacement). | ||||||||||||||
Working Atmosphere | Limiting ambient temperature -40°C~+70°C,Relative humidity (RH) ≤98(25°C),Altitude ≤3000m | |||||||||||||
Main Electric performance | The withstand voltage between the primary and secondary windings is no less than 3kV and insulation resistance is no less than 1GΩ |