Current output of computer communication Temperature Controller XMT8008CK
Outline
Almost intelligent industrial adjustment instrument Syria XMT8008CK 4 ~ 20mA output signal, can control the three-phase voltage regulator module, single-phase voltage regulator module, the module on the current voltage through the phase control (that is, to change the size of the implementation of current and voltage on the load power control), can be connected to the PLC, to achieve temperature display can be connected to the inverter, the motor speed. Instrument with RS485 communication function, and computer communications, to provide a management software. Interface shown in Figure:
Technical Specifications:
1)Input specifications (one meter can be compatible),
2)Thermocouple: K, S, E, J, T, B, N,
WRe thermal resistance: CU50, PT100 linear
3)voltage :0-5V ,1-5V, 0 - 1V ,0-100mV ,0-20mV
4)linear current (with external shunt resistor) :0-10mA ,0-20mA ,4-20mA, etc.
Range:
K(0~1300°C), S(0~1600°C), E(0~800°C), J(0~1000°C),
T(-200~+350°C), B(0~1800°C), N(0~1300°C), Wre(0~2300°C)
CU50(-50~+150°C),PT100(-200~+600°C)
Adjusting:
Position adjustment means (hysteresis adjustable), artificial intelligence, adjustment, including fuzzy logic PID parameter self-tuning regulation and function of advanced control algorithms, control accuracy up to ± 0.2 °C
Output Specifications
1)Output relay contact switch (normally open + normally closed): 250VAC/10A or 30A
2)SSR voltage output: 12VDC/30mA (for driving SSR solid state relay)
3)SCR trigger output: two-way trigger 5-500A control Silicon;
4) two-way reverse parallel SCR or SCR power module
5)Linear current output: 0 ~ 10 mA or 4 ~ 20 mA alarm function can be defined: upper limit, lower limit, positive deviation, negative deviation of 4 kinds of ways a maximum output of 3-way, with the power to remove alarm
EMC:
1)IEC61000-4-4 (electrical fast transient burst), +2 KV/5KHZ;
2)I EC61000-4-5 (Surge) 4KV
3)isolation voltage: power supply side, the relay is triggered and the output terminals between ≥ 2300V;
4)each other isolation between the weak signal end of ≥ 600V
5)manual features: automatic / manual two-way non-disturbance switching power supply :100-240VAC, -15%, +10% / 50HZ; or 24VDC/AC, -15%, +10%.
6)power consumption : ≤ 5W
7)ambient temperature: 0 ~ 50 °C