Temperature transmitter
1)Programmable with HART-protocol
2)Sensor monitoring
3)Galvanic isolation
4)2-wire technology
Minimum Order Quantity: 1 Unit/Units
Supply Ability: 500 Unit/Units per Month
Payment Terms: T/T
Contact SupplierPackaging Detail: standard
Delivery Detail: within 2 weeks after payment received
Configurable HART field temperature converter MS192
Performance
• Universal programmable with HART®-protocol
•Two-wire technology, analog output 4 to 20 mA
•Digital display (LED,LCD)
•Max/Min process value indicator function
•Highly accurate in entire operating temperature range
•Configuration during measurement using a PC or via the HART communication
•Sensor monitoring: Failure conditioning in event of sensor break or sensor short-circuit
•IP67(aluminum alloy casing),IP65(plastic casing)
•Galvanic isolation
Application area
• Field-mounted temperature transmitter for converting various input signals into a standard 4 to 20 mA analog output signal
• Input:RTD,TC,Ohm,mV
• Optional aluminum alloy casing for explosion proof application
• HART® -protocol for front end unit or panel unit operation using the hand operating module (MS275, MS375,PDA N800,PDA S900) or PC
Input
Type | Type | Measurement ranges | Min.meas. Ranges |
Resistance thermometer (RTD) | Pt100 Pt500 Pt1000 acc.to IEC 751 | -200 to 850 °C (-328to1562 °F) -200 to 250 °C (-328 to 482 °F) -200 to 250 °C (-328 to 482 °F) | 10 K 10 K 10 K |
Ni100 Ni500 Ni1000 acc.toDIN43760 | -60 to 180 °C (-76 to 356 °F) -60 to 150 °C (-76 to 302 °F) -60 to 150 °C (-76 to 302 °F) | 10 K 10 K 10 K | |
Resistance transmitter (Ω) | Ω | 10 to 400 Ω 10 to 2000 Ω | 10 Ω 100 Ω |
Thermocouple (TC) | B(PtRh30-PtRh6) C(W5Re-W26Re) D(W3Re-W25Re) E(NiCr-CuNi) J (Fe-CuNi) K (NiCr-Ni) L (Fe-CuNi) N (NiCrSi-NiSi) R (PtRh13-Pt) S (PtRh10-Pt) T (Cu-CuNi) U (Cu-CuNi) acc.toIEC584 Part1 | 0to+1820°C (32to3308°F) 0to+2320°C (32to4208°F) 0to+2495°C (32to4523°F) -200to+915°C (-328to1679°F) -200to+1200°C (-328to2192°F) -200to+1372°C (-328to2501°F) -200to+900°C (-328to1652°F) -270to+1300°C (-454to2372°F) 0to+1768°C (32to3214°F) 0to+1768°C (32to3214°F) -200to+400°C (-328to752°F) -200to+600°C (-328to1112°F) | 500 K 500 K 500 K 50 K 50 K 50 K 50 K 50 K 500 K 500 K 50 K 50 K |
Voltage transmitters (mV) | mV | -10 to 100 mV | 5 mV |
Output
Output signal | analogue 4 to20 mA ; HART –Protocol output |
Transmission behaviour | Temperature linear, resistance linear, voltage linear |
Max-load | (V power supply-13V)/0.025A(Current output) |
Current limit | ≤25 mA |
Signal on alarm | •Underranging linear drop to 3.8 mA •Overranging linear rise to 20.5 mA •Sensor break;sensor short-circuit: ≤3.6mA or ≥21.0mA |
Galvanic isolation | 1500V AC (input/output) |
Electrical connection