Quick Brief

Place of Origin: Zhejiang China (Mainland) Brand Name: blue jay Model Number: DRT-301C Display Type: Digital Only Phase: Single Phase Measuring Energy Range: 0-9999 Accuracy Class: 1.0 Output Voltage: 220V Operating Temperature: -10-50c

Product Features:

1.Double phase three wires energy meter

2.Voltage :230V

3.Current:10(100)A

4.SO output

Business Terms:

Port: hangzhou

Minimum Order Quantity: 10 Piece/Pieces

Supply Ability: 10000 Piece/Pieces per Month

Payment Terms: T/T,Western Union

Contact Supplier
400v 100a kwh meter for industrial use
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: with export package

Delivery Detail: within 7-15days after you order

Specifications and Product Details:

DRT301C

Three phase Din Rail Multi-Tariff energy meter with modbus protocol

Description :

1. CI.1 accuracy (EN50470-1 , EN50470-3 )

2. 4 DIN module

3. 35mm standard DIN rail installation

4. 80A direct current

5. Include 1 , 2 and 4 tariffs meters options

6. RS-485 and far infrared port for communication

7. communication protocol : MODNBUS RTU

8. Two current channel meters option

9. Display electrical units : voltage (V ) , current ( A ) , frequency (HZ ) , Energy ( kwh )

Specification :

Meter Specifications

Nominal Voltage(Un)230/400V AC (3~)
Operational voltage161/279 – 300/520V AC (3~)
AC Voltage Withstand4KV for 1 minute
Impulse Voltage Withstand6kV – 1.2µS waveform
Starting current (Ist)0.04A
Transitional current(Itr)1A
Minimum current0.5A
Reference current (Iref)10A
Maximum current (Imax)65A
The current measuring range0.5-10(65)A
Peak current withstand1950A for 0.01s
Operational frequency range50Hz ±10%
Internal power consumption≤2W / 10VA per phase

Positive & reverse active energy test

output flash rate (Pulse LED)400imp/kWh

Positive & reverse active energy

output pulse rate400imp/kWh

Accuracy Class 1

Voltage, LN & LL (Phase1,2,3)±0.5%
Amps (Phase 1,2,3)±0.5%
Frequency±0.2%
PF (Phase 1,2,3 &Σ)±0.2%
Active power (Phase 1,2,3&Σ)±0.5%
Reactive power (Phase 1,2,3&Σ)±2%
Apparent power (Phase 1,2,3&Σ)±0.5%
Active energy±1%

Infrared Communication Specifications

Infrared Wavelengths900- 1000nm
Baud Rate1200bp
Communication Distance Range5m
Communication Angle-15°~+15
ProtocolDL/T645 -2007

Tariff Specifications

Tariff Number2
Input voltage of tariffs settingPin20&21

0-65V AC, tariff T1 is valid ,tariff T2 is invalid

95-400V AC, tariff T2 is valid, tariff T1 is invalid

Operating Temperature-10°C to +50°C
Operating Humidity≤ 75% non condensing
IP ProtectionIP51
Protective classII
Dimensions140 mm high x 70mm Depth x 70mm Width
Size of connection clamp(L×H)8×8mm
Size of connec clamp(Diagonal)11.3mm
Weight0.5KG(net)

Material

Front panelPC flame resistant plastic
Protection coverABS flame resistant plastic
CoverABS flame resistant plastic
BaseABS flame resistant plastic
400v 100a kwh meter for industrial use suppliers    400v 100a kwh meter for industrial use manufacturers