Home  >  Temperature Instruments

220V Cold storage temperature controller with defrosting - ED106W

refrigerator Temperature control, Evap.Fan Control, Defrost by electric heater,hot gas, Time,temp.setting to end defrost - more info check here: http://www.buymeasuringtools.com/220V-Cold-storage-temperature-controller-with-defrosting-10155960/

Quick Brief

Place of Origin: Guangdong China (Mainland) Model Number: ED106W Usage: Indoor Theory: Temperature Controller

Product Features:

refrigerator Temperature control

Evap.Fan Control

Defrost by electric heater,hot gas

Time,temp.setting to end defrost

Business Terms:

Port: Shenzheng

Minimum Order Quantity: 100 Piece/Pieces

Supply Ability: 2000 Piece/Pieces per Month

Payment Terms: T/T,Western Union

Contact Supplier
220V Cold storage temperature controller with defrosting
Share to: Facebook Twitter LinkedIn Google+

Product Packagings & Delivery Terms:

Packaging Detail: Export cartonneutral packing/Customary Packing with PE Plastic bags to sealTo avoid water and dust each one meter have a corrugated paper case, independent placeTo avoid collision corrugated paper case dimension: 180x130x130 / 150x90x110 / 105x105x125mm

Delivery Detail: 7~15 Working Days

Specifications and Product Details:

Technical Data

Range of temperature display:-45~150°C (-40~150°F)
Range of set temperature:-45~45°C (-40~113°F)
Accuracy:±1.0°C (±1.8°F)
Resolution:0.1°C /°F(—19.9~99.9°C /°F)
Compressor: N.O. 16A/250VAC
Defrost: N.O. 10A/250VAC
Evap.Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm

Parameters

ParameterFunctionSet raneDefault
E1Lower setpoint limit-45°C/-45°F~Set temp.-35°C/-31°F
E2Higher setopint limitSet temp.~45°C/113°F45°C/113°F
E3Temp.hysteresis1~20.0°C / 1.8~36.0°F4.0°C/7.2°F
E4Comp.start delay time0~10Min2Min
E5Offset on room temp.-20.0~20.0°C / -36.0~36.0°F0
E6Offset on evap.temp.-20.0~20.0°C / -36.0~36.0°F0
C1Temperature unit0=°C 1=°F0
F0Defrost function0=Electric heater 1=Host gas0
F1Max.defrost duration1~60Min20Min
F2Defrost interval time0~24Hr6Hr
F3Defrost terimination temp.0~30°C / 32~86°F8°C/46
F4Display during defrost0=Nomal display

1=Last value before defrost

0
F5Fan operationg fuction0=Parallel with comp.

1=Continuous running except defrost

0
F6Dripping time0~30Min2
F7Fan operating fuction after defrost end0=Temperature 1=Time1
F8Fan start-up delay after defrost end0~10Min2
F9Fan start temperature after defrosting(evaporator)-30~30°C / -22~86°F5°C/41°F
220V Cold storage temperature controller with defrosting suppliers    220V Cold storage temperature controller with defrosting manufacturers